Generally, the power distribution room of newly-built residential areas is often set in the first floor or basement of buildings. When it is installed on the first floor of a building, care should be taken not to be directly below the toilet, bathroom and other places where water often accumulates. When the residential power distribution room is set in the basement of the building, it should be noted that the ground elevation in the power distribution room is 10cm higher than the outdoor ground elevation to prevent outdoor water from infiltrating into the power distribution room.
Extended data:
Precautions:
The layout is compact and reasonable, which is convenient for the operation, handling, maintenance, test and inspection of the equipment, and the possibility of development should also be considered.
Reasonably arrange the relative positions of the rooms in the building, so that the location of the distribution room is convenient for entering and leaving the line.
Make full use of natural lighting and ventilation. The transformer room and capacitor room should be protected from western sunlight, and the control room should face south as far as possible.
The ground of power distribution room, control room and duty room shall be higher than the outdoor ground 150~300mm. When it is attached to the workshop, it can be flush with the floor of the workshop.
10kV distribution substation should be arranged in a single floor. When double-deck layout is adopted, the power distribution room should be located on the ground floor, and the second-floor power distribution room should be provided with lifting holes and platforms for lifting equipment.
Baidu encyclopedia-distribution room